Description

CHQ-DZM(SCI) – Hochiki Dual Zone Monitor with SCI

Model CHQ-DZM(SCI) is a Dual Circuit Zone Controller designed to allow up to 60 conventional detectors (30 on each zone) to be interfaced to Hochiki’s ESP analogue addressable system.  The unit also features a Schottky Diode line continuity option, when used in conjunction with the optional LCMU.

Full monitoring against malfunction or disconnection, together with a self-test feature through the ESP protocol, ensure the integrity of the CHQ-DZM(SCI) at all times.  The CHQ-DZM(SCI) utilises simple DIL switches for reliable addressing.  It is available as an OEM version (as illustrated above) and also as a DIN Rail mountable module (CHQ-DZM/DIN(SCI)).  Both models feature an integral short-circuit isolator.

Please note: When Resistive EOL option is chosen the conventional zone on the CHQ-DZM(SCI) does not support any line continuity options, therefore if Call Points are being interfaced they should be wired at the beginning of the zone.

Key Features:

  • Single loop address
  • Supports two independent zones of conventional detectors
  • Both zones fully monitored for short/open circuit
  • Requires an auxiliary 24 V dc supply
  • DIN rail version available
  • Both models feature an integral short-circuit isolator
  • Approved by LPCB