Description
55000-797APO – Apollo XP95 DIN-Rail Mains Switching Input / Output Unit
The DIN-Rail Mains Input/Output Unit provides a mains-rated voltage-free, single pole change-over relay output and a monitored switch input. The unit supervises one or more normally-open switches connected to a single pair of cables.
Device Addressing:
The address of the Input/Output Unit is set using the lower seven segments of the DIL switch. Each segment of the switch must be set to “0” or “1”, using a small screwdriver or similar tool. For complete list of address settings refer to Installation Guide (39214-449).
Key Features:
- It can report fault, switch open and switch closed levels
- Three visible LEDs
- Capable of switching up to 8A at 250V AC
- Fits a standard 35mm DIN-Rail