Description

55000-001APO – Intelligent Open-Area Sounder (Red)

The Intelligent Open-Area Sounder has been designed for use in open areas and can be connected to any Discovery or XP95 system.

Operation

A nominal sound output of 100dB(A) is achieved at a current consumption of 5mA in the case of the sounder and 8mA for the sounder beacon. Many control panels will be able to drive up to 20 sounders and up to 15 sounder beacons per loop on average. The maximum number of devices that may be connected to a particular loop should, however, be determined by a loop loading calculation using the Apollo Loop Calculator. This is available via the Apollo website www.apollo-fire.co.uk. Since the alarm devices are intended for use in open areas, it is possible for more than one device to be audible at any given point in a building. For this reason, the operation of all may be synchronised by the control panel. All the alarm devices can be assigned group addresses as well as individual addresses, so that the functional options of the sounder are identical with those of the Sounder Control Unit part no 55000-582 or 55000-182 (DIN-rail version).

Key Features
  • Self-test fault monitoring
  • Choice of tones on standard device: Apollo, Slow Whoop and DIN
  • Two volume settings 92dB(A) and 100dB(A)
  • Synchronisation of tones
  • Individual and group addressing
  • Built in isolator
  • Red or white options
  • Loop-powered IP65 rated